Measurement
NANOVIP® DE™
Remote electrical device
Portable MRH™ remote analyzers of power quality
NANOVIP® DE™ is a remote measuring device for MRH™ networks; it can performe all electrical measurements and send them to a NANOVIP® QUADRA™ master device that will assemble all network parameters.
NANOVIP® DE™ is fully driven by a NANOVIP® QUADRA™ master device and an MRH™ network can include up to 5 NANOVIP® DE™ devices connected to a master; electrical mesurements set is including all its related NANOVIP® CUBE™ analyzer.
When DE is connected, all data are available on its display as well as they can be red in realtime from the NANOVIP® QUADRA™ Master device.
Extreme easy to use and setup because it just require to be assigned with a role in the network, then the NANOVIP® QUADRA™ master analyzer will set network parameters accordingly.
Measurements everywhere,
safely
safely
- Self setting wireless network connection
- Max indoor point to point distance: 60m
- Max outdoor point to point distance: 600m
- MRH network client mode
- Can work on networks: single-phase, two-phase, three-phase balanced with or without neutral, three-phase unbalanced with or without neutral
- Full traditional energy analysis (V, I, P, Q, S, F, PF, THD%, instantaneous values / minimum / maximum / average, energy meters absorbed and generated both three-phase for each phase).
- Can measure heterogeneous energies and power: solar, elevtrical loads, generators, storage systsems, multiple grid connections, eolic, UPS, inverters etc
- The current and voltage harmonics for each phase and for the neutral up to 50°
- Imbalance of power phases
- Real measurement of the neutral current
- Display of the waveforms of currents and voltages
- Display of the time course of selectable parameters (trend)
- Automatic check of the correct connection of the implant tool
- Realization of long-term measurement campaigns (over 24 independently, unlimited if connected to the network)
- Multilanguage
- Customizable display, choosing which values display in rotation in the lower part and rotating it 90 ° in relation to the comfort of reading
Fields of use
NANOVIP® DE™ is a powerfull remote power quality analyzer to be connected to a NANOVIP® QUADRA™ master device; NANOVIP® DE™ can perform a wide spectrum of electrical measures and send them to master device to be realtime combined with other measures retrieved by additional remote measure points.
All measures are available on its display as well as from the master device.
Thanks to its flexible MRH™ technology it can:
- measure and monitor all power quality parameters in a point of a newtork
- store data locally and share it with the master device of the network for global network parameters calculation
- operate as: Load, Grid, Generator, Storage, Inverter, Event and single point
- combined with a master device in Solar mode it can patrol a solar set
- catch events
- patrol a grid connections
- check and evaluate the performance of UPS, Inverters
- measure AC and/or DC lines in the net
- measure signals for non-symmetric PWM control of inverter
- identify the presence of harmonics, outages, overloads or potentially harmful voltage dips for machinery and equipment in the network
- intercept fluctuations and rapid changes in current and voltage signals
Standard | IEC61000-4-30 Class S |
Dimensions | 203x116x53mm |
Safety | 600V CAT III |
Protection degree | IP30 |
Weight | 580g. |
Display type | LCD dot matrix with backlight |
Communication | USB to PC, wireless to master |
Onboard memory | 64kB |
External memory | Micro SD (4GB supplied) |
MRH master operating mode | no |
MRH client operating mode | yes |
Standalone | no |
Single point monitoring | yes |
AC measurements | yes |
DC measurements | yes |
Solar measurements | no |
Solar panel and strings test CEI 8225 | no |
Multilines solar system test CEI 8225 | no |
Solar realtime measurements | no |
Solarmeter interface | no |
Temperatures interface | no |
Wind speed interface | no |
General transducers interface | no |
Harmonics | yes |
Transients | no |
Inrush | no |
Wave form | yes |
Counters | yes |
Alarms | no |
Active, Reactive and Apparent P, E | yes |
Tariffs | no |
EN50160 test | no |
QUADRA Studio software | included |
Indoor wireless point to point distance | 60m |
Outdoor wireless point to point distance | 600m |
Working temperature range | from -10 to +55 °C |
Umidity | Max 95% |
External power supply | Wall-plug switching, input 100-240VAC ±10% 47-63Hz, changeable plug; output 7,5VDC – 12W |
Battery | 4 x AA MiMh 2100mAh |
Autonomy | >24h |
Languages | English- Spanish – Italian – German – French |
MRH technology | yes |
Standalone mode | yes |
Single phase/Double phase networks | yes |
Three phase 4 wires, balanced networks | yes |
Three phase 3 wires, balanced networks | yes |
Three phase 4 wires, unbalanced networks | yes |
Three phase 3 wires, unbalanced networks | yes |
Solar measurements | yes |
Power analisys | V, I, P, Q, S, F, PF, THD(V)%, THD(I)%, cosj, j, peaks, min, max, mid, max. demand, ecc. |
Counters | kWh, kVArh, kVAh (used and generated) |
Waves shape | V e I |
Harmonics | Values and spectrum up to 50° |
Sags | Dips, swells and net interruption |
Transitory | Overcurrent and overtension |
Test EN 50160 | yes |
Starting currents | yes |
Measurements in DC | yes |
K factor | Up to 25° |
Alarms | Video |
Alarms logs | 5 on video |
Hourly tarifs | up to 4 |
Consumption costs | yes |
Measurement campaign | Unlimited, up to SD completition |
Display data refres | 1 sec. |
Voltage (TRMS) | 4 input channels (3 + common neutral + 1 auxiliary) |
Current (TRMS) | 5 input channels |
Power | Active, reactive and apparent. Single phase and total |
Energy counters | kWh, kvarh, kVAh |
Harmonics analisys | Up to 50° |
EN50160 analisys | from 500mS up |
EN61724 analisys | potentially unlimited |
Test CEI 82-25 | yes: standalone and network |
Transitional analisys | Overcurrent, overvoltage and starting currents |
CE conformity | 93/68/CEE (B.T. electrical materials); |
89/336/CEE e 2004/108/CE (EMC) | |
2006/95/CE – 72/23/CEE (LVD – Low voltages); | |
2002/95/CE (RoHS – Dangerous materials restrictions); | |
2002/96/CE e 2003/108/CE (WEEE/RAEE – Wasted electrical and electronics materials). | |
Safety | EN 61010-1 |
EMC | EN 61326 |
EN 61326/A1 | |
EN 61326/A2 | |
EN 61326/A3 | |
Temperature | IEC 60068-2-1 (working) |
IEC 60068-2-2 (storage) | |
Vibrations | IEC 60068-2-6 |
Umidity | IEC 60068-2-30 (umidity) |
Overload | IEC 60947-1 |
4NAN3N | NANOVIP/CUBE WITHOUT CLAMPS |
4NAN3 | NANOVIP/CUBE WITH 3xNANOFLEX CLAMP 400mm 3kA |
4NAN3A | NANOVIP/CUBE WITH 3xCLAMP CT 200A/1VAC |
4NAN3B | NANOVIP/CUBE WITH CLAMPS 3x200A + 3x3kA |
4NAN3C | NANOVIP/CUBE WITH CLAMPS 3x5A + 3x200A + 3x1000A |