Measurement
Brochure NanoVIP® ONE™ 290kb 331 downloads
Power Quality analyzer for monophase, three phase balanced AC and DC networks ...
NANOVIP® ONE™
Portable power quality analyzer
NanoVIP® ONE™ is a modern power quality analyzer equipped with all the functions necessary for measuring and monitoring both electricity consumption and the main power quality parameters.
It can be used on single-phase and three-phase balanced networks in low and medium voltage as well as on DC systems.
Particularly compact in size, it uses commercial AA batteries (rechargeable or not), has a considerable internal storage capacity (4Gb) and a graphic display.
An affordable analyzer but suitable for professional use.
Light, compact and powerful
- Leggero, maneggevole, multilingua, con performaces e caratteristiche al top della sua categoria
- 128×128 graphic LCD that allows a wide display flexibility (multilingual menu, waveforms, histograms, diagrams, images, etc.)
- Dedicated NanoStudio PC software through which it is possible to perform advanced analyzes of stored data
- 1 voltage measurement channel (1 phase + neutral) up to 600V CAT III, with the possibility of measuring also the DC voltage, with an accuracy of ± 0.5% + FS error
- 1 current input with the possibility of measuring also the DC current, with the accuracy of ± 0.5% + FS err
- Capability to use flexible clamps up to 6000A or other sensors with full scale set by the user
- Can be used with AA commercial batteries (rechargeable or not) or with external power supply (optional) for prolonged campaigns
- Alarms (generic, overvoltages ect) settable by user
- 4Gb internal memory for measurements savings
- Multifunction keyboard
- USB output for download/upload measurements, setup and remote control
- Buzzer for errors and alarms
- Harmonic analysis up to the 25th degree
- Oscillo function for continuous capture of a channel (rms voltage or current)
- Start/Stop counters function for quick consumption analysis
impieghi
NanoVIP ONE is a handy, compact and lightweight tool aimed at both those who want to work on their systems and professionals in the sector who need detailed and precise energy quality analyzes; NanoVIP, thanks to a wide range of functions, allows in an easy and intuitive way to :
- Keep loads, consumption and related network costs under control
- Check in service the correct sizing of the systems
- Analyze the instantaneous variation of current and voltage thanks to the Oscillo function
- Verify, by continuously storing the last 30 minutes of the main electrical measurements, the progress of the system in the minutes preceding an event.
- Dimensioning the reactive power necessary for the power factor correction of a plant.
- Correctly solve the system power factor correction problems
- Monitor load peaks and power exceedances in order also to reduce the contractual electrical commitment
- Verify and evaluate the performance of UPS, with ac / dc measurements;
- Identify the presence of harmonics and overloads that are potentially harmful to machinery and systems
- Intercept rapid fluctuations and changes in current and voltage signals
Standard | IEC61000-4-30 Class S |
Dimensions | 178x80x32mm |
Material | ABS with self-extinguishing V0 grade |
Safety | 600V CAT III |
Protection degree | IP30 |
Weight | 220g (315g incluse le batterie) |
Display | LCD 128×128 STN dot matrix retroilluminato bianco |
Languages | Inglese – Spagnolo – Italiano – Tedesco – Francese |
Communication | USB verso PC |
Internal memory | 4Gb |
Operating temperature | da -10 a +55 °C |
Umidity | Max 95% |
Power supply (optional) | Wall-plug switching extern, input 100-240VAC ±10% 47-63Hz, with international plugs; output 7,5VDC – 12W |
Included batteries | 4 x AA 1,5V |
Autonomy | >72h (depending on battery type) |
Single phase/Double phase networks | yes |
Three phase 4 wires, balanced networks | yes |
Three phase 3 wires, balanced networks | yes |
Three phase 4 wires, unbalanced networks | no |
Three phase 3 wires, unbalanced networks | no |
Power analisys | V, I, P, Q, S, F, PF, THD(V)%, THD(I)%, cosj, j, peaks, min, max, mid, max. demand, ecc. |
Counters | kWh, kVArh, kVAh (used and generated) |
Waves shape | V e I |
Harmonics | Values and spectrum up to 25° |
Sags | no |
Transitory | manual |
Test EN 50160 | no |
Starting currents | no |
Measurements in DC | yes |
K factor | no |
Alarms | Video |
Alarms logs | 5 on video |
Hourly tarifs | no |
Consumption costs | no |
Measurement campaign | On internal memory, exportable to PC via USB |
Display data refres | 1 sec. |
Voltage (TRMS) | 1 input channel 4MOhm, 2 scales |
Current (TRMS) | 1 input channel 10kOhm |
Power | Active, reactive and apparent. Single phase and total |
Energy counters | kWh, kvarh, kVAh |
Harmonics analisys | Up to 25° |
EN50160 analisys | no |
Transitional analisys | manual |
Conformità CE | 93/68/CEE (materiale elettrico in B. T.); |
89/336/CEE e 2004/108/CE (EMC – Compatibilità Elettromagnetica) | |
2006/95/CE – 72/23/CEE (LVD – Bassa Tensione); | |
2002/95/CE (RoHS – Restrizioni all’uso di Sostanze Pericolose); | |
2002/96/CE e 2003/108/CE (WEEE/RAEE – Rifiuti Apparecchiature Elettriche ed Elettroniche). | |
Sicurezza | EN 61010-1 |
Compatibilità elettromagnetica (EMC) | EN 61326 |
EN 61326/A1 | |
EN 61326/A2 | |
EN 61326/A3 | |
Temperatura | IEC 60068-2-1 (temperatura di funzionamento) |
IEC 60068-2-2 (temperatura di conservazione) | |
Vibrazioni | IEC 60068-2-6 |
Umidità | IEC 60068-2-30 (umidità) |
Sovraccarico | IEC 60947-1 |
4NAN1 | NANOVIP ONE CON PINZA 1x100A |
4NAN1A | NANOVIP ONE CON PINZA 1x200A |
4NAN1N | NANOVIP ONE SENZA PINZA |
Item | Quantity | Standard/Option |
NanoVIP® ONE™ | 1 | Standard |
Battery AA 1.5V | 4 | Standard |
Voltage cables | 2 | Standard |
Crocco | 1 | Standard |
Packing | 1 | Standard |
Calibration certificate | 1 | Standard |
Clamps/current sensors AC | 1 or more | Optional – According to kit |
Current clamp DC | 1 or more | Optional – According to kit |