Misurazione
AC/DC amperometric clamp PAC11
– Phased out –
AC/DC amperometric clamp for NanoVIP® power quality analyzers
Amperometric clamp based on Hall effect to measure AC (up to 400 A) and DC currents (up to 600 A) with an high end precision all over the measurement range.
Versatile, easy to use and powerful
- Can be used on NanoVIP® family analyzers without the need for external power supply or amplification.
- Equipped with automatic recognition system if used on the latest NanoVIP® series analyzers: TWOTM, CUBETM and QUADRATM
- Designed for the measurement of alternating currents up to 400V and direct currents up to 600V
- Double scale
- Robust and reliable
- The grippers can grip conductors up to 30 mm in diameter.
- Automatic stand-by can be bypassed
- The precision that it offers on the whole measuring range allows it a very wide use (from civil to industrial)
- The shape allows a safe use even when wearing safety gloves
- Optionally adapters are available to use it on older generation of Elcontrol analyzers, without automatic clamp recognition
Characteristics
The PAC11 is a Hall-effect current clamp for measuring direct and alternating currents.
This clamp has 2 scales for better measurement resolution and accuracy, it includes a simplified ZeroDC adjustment system and the possibility to deactivate the automatic standby function.
PAC11 AC/DC clamp can be used on all the analyzers of the latest generation of NanoVIP® family (production from 2015 onwards with automatic recognition of the current clamps) including the DS model for PV panels output.
For the older NanoVIP® analyzers (without clamps recognition), suitable adapters are available to allow their use.
Brochure DC current clamp SC3C 139kb 49 downloads
Brochure of 1000A DC current clamp for NanoVIP® power quality analyzers ...Measured range | AC: 0,2 A up to 400A (600A peak) DC: 0,4 A up to 600A |
Operating voltage | 600V rms |
Overload | 2000A DC and 100A AC up to 1kHz |
Bandwidth | DC…10 kHz at -3dB |
Common mode voltage | 600 V rms |
Influence of adjacent conductor: | < 10mA/A at 50 Hz |
Influence of conductor position in jaws: | 0.5 % of the reading |
Influence of DC current >20A overlying on the nominal current: | < 1% of output signal for a current ≤ 30A DC |
Battery | 9V alkaline |
Battery lasting time | 50 hours |
(1) Conditions of reference | 23 °C ± 5 °K, 20% to 75% RH Continuous external DC magnetic field (earth field) < 40 A/m Absence of external AC magnetic field External electrical field < 1 V/m Position of conductor measured: centred in the measurement coil Shape of measurement coil: quasi-circular Measurement instrument input impedance (oscilloscope) ≥ 1 MΩ Frequency and form of signal measured: 40 to 400 Hz sinusoidal |
Electrical safety | Class II equipment with double or reinforced insulation between the primary and the secondary (winding connected to the connection cable) as per EN 61010-1 & EN 61010-2-032: – 1000V CAT III, pollution degree 2 – 600V ACT III, pollution degree 2 – Type-B sensor |
Dimensions | 224 x 97 x 44 mm |
Weight | 440g |
Operating temperature | -10 °C to +55 °C |
Storage temperature | -40 °C to +80 °C |
Influence of temperature: | < 300 ppm/°K or 0.3%/10 °K < 0.3 A/°K |
Relative humidity for operation: | +10 °C to 35 °C: 90 ±5% RH (without condensation) +40 °C to 55 °C 70 ±5% RH (without condensation) |
Influence of relative humidity: | from 10% to 90% RH at reference temperature: < 0.1% |
Operating altitude | 0 to 2000 m (for 600V CAT III) |
Clamping capacity: | 1 cable Ø 30mm or 2 cables Ø 24mm or 2 busbars 31.5x10mm |
Drop test: | 1 m on a 38mm container of oak on concrete, test in accordance with IEC 1010 |
Shock resistance: | 100 g in accordance with IEC 68-2-27 |
Vibration resistance: | 5/15 Hz 1.5 mm; 15/25 Hz 1 mm; 25/55 Hz 0.25 mm; (IEC 68-2-6) |
Self-extinguishing capability | Casing: UL94 V2 Jaws: UL94 V0 |
4AABUS | AMPEROMETRIC AC/DC CLAMP PAC11 |