Measurements
Current clamp MN13
AC current clamp for NanoVIP® power quality analyzers
Amperometric mini-clamp for AC currents from 0.5 A to 200 A with with reduced dimensions and high ergonomics.
Compact, strong and precise
- Can be used on NanoVIP® family analyzers without the need for external power supply or amplification.
- Equipped with automatic recognition system if used on the latest NanoVIP® series analyzers: TWOTM, CUBETM and QUADRATM
- Designed for the measurement of alternating currents in a wide range of values: from 0.5A to 200A
- Compact and light
- The shape of the pliers makes it easy to hook onto the cables, even in the smallest areas.
- The grippers can grip conductors up to 20 mm in diameter.
- The precision that it offers on the whole measuring range allows it a very wide use (from civil to industrial)
- The shape allows a safe use even when wearing safety gloves
- Optionally adapters are available to use it on older generation of Elcontrol analyzers, without automatic clamp recognition
Characteristics
The MN13 current clamp can be used on all analyzers of the NanoVIP® family to measure AC currents up to 200 A; it is equipped with an automatic recognition system by the analyzer that makes its setting very simple.
The particularly compact dimensions make it a highly ergonomic tool, easy to place and with minimal space requirements.
MN13 AC clamp can be used on all the analyzers of the latest generation of NanoVIP® family (production from 2015 onwards with automatic recognition of the current clamps) except for the DS model that can only mount the DC clamp.
For the older NanoVIP® analyzers (without clamps recognition), suitable adapters are available to allow their use.
Brochure current clamp MN13 494 kb 264 downloads
Brochure of 200A AC current clamp for NanoVIP® power quality analyzers ...Measured range | 0,5 A up to 240A |
Operating voltage | 600V rms |
Output signal | 5 mV AC / A AC (1,2 V for 240A) |
Bandwidth | 40 Hz …10 kHz |
Crest factor | 3 for a current of 200A rms |
Maximum currents | 200 A continuous for a frequency ≤ 1 kHz (derating proportional to the inverse of frequency beyond) |
Common mode voltage | 600 V category III and pollution degree 2 |
Influence of adjacent conductor: | ≤ 15mA / A at 50 Hz |
Influence of conductor position in jaws: | ≤ 0.5 % of output signal at 50 / 60 Hz |
Influence of DC current >20A overlying on the nominal current: | ≤ 5% |
Influence of frequency(2): | < 3% of output signal from 40Hz…1kHz < 12% of output signal from 1kHz…10kHz |
Influence of crest factor: | < 3% of output signal for a crest factor of 3 and current of 200A rms |
Electrical safety | Class II equipment with double or reinforced insulation between the primary and the secondary (winding connected to the connection cable) as per EN 61010-1 & EN 61010-2-032: – 1000V CAT III, pollution degree 2 – 600V ACT III, pollution degree 2 – Type-B sensor |
(1) Conditions of reference | 23 °C ± 5 °K, 20% to 75% RH Continuous external DC magnetic field (earth field) < 40 A/m Absence of external AC magnetic field External electrical field < 1 V/m Position of conductor measured: centred in the measurement coil Shape of measurement coil: quasi-circular Measurement instrument input impedance (oscilloscope) ≥ 1 MΩ Frequency and form of signal measured: 40 to 400 Hz sinusoidal |
(2) | Out of reference domain |
Dimensions | 135x51x30 mm |
Weight | 180g |
Operating temperature | -10 °C to +55 °C |
Storage temperature | -40 °C to +70 °C |
Influence of temperature: | ≤ 15% of output signal per 10 °K |
Relative humidity for operation: | 0 to 85% RH decreasing linearly above 35 °C |
Influence of relative humidity: | < 0.2 % of output signal from 10% to 85% RH |
Operating altitude | 0 to 2000 m (for 600V CAT III) |
Storage altitude | ≤ 12000m |
Clamping capacity: | Cable: Æ max 20 mm Busbar: 1 busbar of 20 x 5 mm |
Drop test: | 1 m (IEC 68-2-32) |
Shock resistance: | 100 g 6 ms ½ period (IEC 68-2-27) |
Vibration resistance: | 10/55/10 Hz, 0.15mm (IEC 68-2-6) |
Casing protection rating | IP40 (IEC 529) |
Self-extinguishing capability | Casing: UL94 V2 Jaws: UL94 V0 |
4AR10RP | MN13 AC CURRENT CLAMP 200A WITH RECOGNITION |