MEASUREMENT

PolarEnergy_MAIN

POLAR AIR

Polar AIR is a multifunctional panel instrument (96 x 96 mm.) of the POLAR family, particularly oriented to the remote monitoring of electrical energies.
It features a highly visible 128×128 graphic display and convenient front keys for direct consultation and setup. It has a wide range of electrical measurements like all models in the POLAR series.

The AIR model can mount multiple communication options to allow maximum flexibility in organizing and configuring a monitoring network.

WiFi communication, together with Elcontrol’s free Energy Studio Free cloud, offers a quick and economical solution for implementing a monitoring network.

The connections to the power cables and to the voltage and current measurement cables are made via the 2.5 mm2 terminals located on the back of the instrument.

To measure the currents it is necessary to use three CTs with a secondary 5 A.

It can be used on single-phase, two-phase, three-phase low and medium voltage networks. The advanced functions and the supplied analysis software make it a tool suitable for the most demanding professional needs.

Focused on communication

  • Reduced dimensions in depth in the panel
  • IP65 front panel
  • Switching power supply 90/230 and 90/300 Vac Vdc (+ 24-48 Vdc option)
  • Scalable thanks to the plug & play options to insert posteriorly
  • 3 measuring channels of voltage up to 600V CAT III with the precision of 0.5%
  • 4 distinct current inputs, with 0.5% accuracy
  • 6 different electrical systems analyzed (single-phase, two-phase, three-phase 3-wire unbalanced, three-phase 4-wire unbalanced, balanced three-phase 3-wire, three-phase 4-wire balanced)
  • Multilingual
  • Customizable display, choosing which values display in rotation in the lower part and rotating it 90 ° in relation to the comfort of reading

Field of use

Polar Energy includes a powerful analysis and calculation engine that allows for a wide range of measurements and features:

  • Standard measures also according to IEC 61000-4-30 of V, I, P, Q, A, F, PF, THD%, instantaneous values / min / max / avg, absorbed and products, energy meters (kWh, KVA , kVAr) absorbed and generated;
  • Graphical display of TREND (trends over time) of 6 selectable sizes
  • Automatic connection test to determine if the connections of the voltages and currents are correct
  • Customization of the user display, which can independently choose which values to keep under control
  • Possible to set alarms
  • WiFi e MRH connectivity for a maximum flexibility
  • With WiFi option, it can be directly connected to Energy Studio Free
Internal dimensions 96x96x58 mm or 96x96x96 mm (with option)
Overall dimensions 96x105x40 mm or 96x105x77 mm (with option)
Safety 600V CAT III
IP protection IP65 front side, IP30 inside panel
Weight 320g + 35g each option
Type LCD dot matrix with white backlight
Languages English – Spanish – Italian – German – Franch
Electrical connections Screw terminals
Communication 485 (option)
Temperature range from -10 to +55 °C
Umidity Max 95%
AC Power supply 90-230V ±10% 50-60Hz 8VA
DC power supply 90-300V ±10% 8W, 12-24V ±10% (option), 48-60V ±10% (option)
Consumption 5VA
Wires section 2,5mm
Single Phase / Two Phase Systems
Three – phase, 4 – wire, balanced and non
3 – wire, balanced and non
VOLTAGE (TRMS)
Channels 3 channels + neutral channels in common
Direct Phase-Phase Measurements Phase-Phase 17-700VAC 40-70Hz, Phase-Neutral 10-400VAC 40-70Hz
Measurements across VT Ratio 1-60000, maximum displayed value 20MV
Permanent load 800VAC
Sensitivity 10V Phase-Neutral, 17 Phase-Phase
Wires section 2,5mm2
CURRENT (TRMS)
Channels 4 independent channels with resistor
Consumption < 1VA
Scales 2
Direct measures not available
Maximum measurable current 8A
Measures across TA Ratio 1:60000, maximum displayed value 500kA
Permanent overload 10A
Temporary overload 50A 1 sec
Sensitivity 10mA
Wires section 2,5 mm2
POWERS
Per each phase < 999 GW,Gvar,GVA
Global < 999 GW,Gvar,GVA
CURRENT (TRMS) 5 independent inputs
POWERS Active, reactive e apparent. Single phase and total
ENERGY COUNTERS
Measures kWh, kvarh, kVAh
ACCURACY
Voltages ±0.25% + 0.05%FS
Currents ±0.25% + 0.05%FS
Powers ±0.5% + 0.05%FS
Power factor ±0.5°
Frequency ±0.01 Hz (40-70Hz)
Active energy Class 0.5
Reactive energy Class 1
EN50160 (only TOP)
Interruptions >500mS
Voltage drops >500mS
Overloads >500mS
CE conformity 93/68/CEE (B. T.);
89/336/CEE e 2004/108/CE (EMC)
2006/95/CE – 72/23/CEE (LVD);
2002/95/CE (RoHS);
2002/96/CE e 2003/108/CE (WEEE/RAEE)
Safety EN 61010-1
Electromagnetic compatibility (EMC) EN 61326
EN 61326/A1
EN 61326/A2
EN 61326/A3
Temperature IEC 60068-2-1 (working)
IEC 60068-2-2 (storage)
Vibrations IEC 60068-2-6
Umidity IEC 60068-2-30
Overload IEC 60947-1
4CAAA POLAR AIR
4ABAE CONVERTITORE USB/RS485
4A485 OPZIONE RS485
4AALM OPZIONE 2 ALLARMI
4ADIN OPZIONE 2 DIGIT
4AVDC OPZIONE 12-24
41VDC OPZIONE 48-60 VDC
city-e