MEASUREMENT
POLAR ENERGY
Precise, reliable and flexible
Panel mounted Energy analyzer
Polar Energy (the successor of the Elcontrol VIP 396 energy analyzer) is a multifunctional panel (96 x 96 mm) mounted tool, ideal for remote measurement, display and remote monitoring of electrical quantities.
It features a 128×128 graphic display of great visibility and comfortable frontal buttons for direct consultation and setup. It has a wide range of electrical measurements.
Compared to the predecessor VIP396, it adds many functionalities that make Polar Energy a modern and user-friendly tool for the user such as the introduction of cyclic connection verification to make installation easy and secure.
The connections to the power cables and to the cables of the voltages and currents are carried out via the 2.5 mm2 terminals in the back of the instrument.
For the calibration of the currents, it is necessary to use three TAs with a secondary 5 A.
It can be used on single-phase, two-phase, three-phase low and medium voltage networks. Advanced features and included analysis software make it an ideal tool for the most demanding professional needs.
Powerfull and flexible
Reduced dimensions in depth in the panel
IP65 front panel
Switching power supply 90/230 and 90/300 Vac Vdc (+ 24-48 Vdc option)
Scalable thanks to the plug & play options to insert posteriorly
3 measuring channels of voltage up to 600V CAT III with the precision of 0.5%
4 distinct current inputs, with 0.5% accuracy
6 different electrical systems analyzed (single-phase, two-phase, three-phase 3-wire unbalanced, three-phase 4-wire unbalanced, balanced three-phase 3-wire, three-phase 4-wire balanced)
Multilingual
Customizable display, choosing which values display in rotation in the lower part and rotating it 90 ° in relation to the comfort of reading
Field of use
Polar Energy has a powerful engine of analysis and calculation that allows a wide range of sizes and capabilities:
Standard measures also according to IEC 61000-4-30 of V, I, P, Q, A, F, PF, THD%, instantaneous values / min / max / avg, absorbed and products, energy meters (kWh, KVA , kVAr) absorbed and generated;
Graphical display of TREND (trends over time) of 6 selectable sizes
Automatic connection test to determine if the connections of the voltages and currents are correct
Customization of the user display, which can independently choose which values to keep under control
Possible to set alarms
485 connectivity
Digital input
Internal dimensions | 96x96x58 mm or 96x96x96 mm (with option) |
Overall dimensions | 96x105x40 mm or 96x105x77 mm (with option) |
Safety | 600V CAT III |
IP protection | IP65 front side, IP30 inside panel |
Weight | 320g + 35g each option |
Type | LCD dot matrix with white backlight |
Languages | English – Spanish – Italian – German – Franch |
Electrical connections | Screw terminals |
Communication | 485 (option) |
Temperature range | from -10 to +55 °C |
Umidity | Max 95% |
AC Power supply | 90-230V ±10% 50-60Hz 8VA |
DC power supply | 90-300V ±10% 8W, 12-24V ±10% (option), 48-60V ±10% (option) |
Consumption | 5VA |
Wires section | 2,5mm |
Single Phase / Two Phase Systems | – |
Three – phase, 4 – wire, balanced and non | – |
3 – wire, balanced and non | – |
VOLTAGE (TRMS) | |
Channels | 3 channels + neutral channels in common |
Direct Phase-Phase Measurements | Phase-Phase 17-700VAC 40-70Hz, Phase-Neutral 10-400VAC 40-70Hz |
Measurements across VT | Ratio 1-60000, maximum displayed value 20MV |
Permanent load | 800VAC |
Sensitivity | 10V Phase-Neutral, 17 Phase-Phase |
Wires section | 2,5mm2 |
CURRENT (TRMS) | |
Channels | 4 independent channels with resistor |
Consumption | < 1VA |
Scales | 2 |
Direct measures | not available |
Maximum measurable current | 8A |
Measures across TA | Ratio 1:60000, maximum displayed value 500kA |
Permanent overload | 10A |
Temporary overload | 50A 1 sec |
Sensitivity | 10mA |
Wires section | 2,5 mm2 |
POWERS | |
Per each phase | < 999 GW,Gvar,GVA |
Global | < 999 GW,Gvar,GVA |
CURRENT (TRMS) | 5 independent inputs |
POWERS | Active, reactive e apparent. Single phase and total |
ENERGY COUNTERS | |
Measures | kWh, kvarh, kVAh |
ACCURACY | |
Voltages | ±0.25% + 0.05%FS |
Currents | ±0.25% + 0.05%FS |
Powers | ±0.5% + 0.05%FS |
Power factor | ±0.5° |
Frequency | ±0.01 Hz (40-70Hz) |
Active energy | Class 0.5 |
Reactive energy | Class 1 |
EN50160 (only TOP) | |
Interruptions | >500mS |
Voltage drops | >500mS |
Overloads | >500mS |
CE conformity | 93/68/CEE (B. T.); 89/336/CEE e 2004/108/CE (EMC) 2006/95/CE – 72/23/CEE (LVD); 2002/95/CE (RoHS); 2002/96/CE e 2003/108/CE (WEEE/RAEE) |
Safety | EN 61010-1 |
Electromagnetic compatibility (EMC) | EN 61326 EN 61326/A1 EN 61326/A2 EN 61326/A3 |
Temperature | IEC 60068-2-1 (working) IEC 60068-2-2 (storage) |
Vibrations | IEC 60068-2-6 |
Umidity | IEC 60068-2-30 |
Overload | IEC 60947-1 |
4BAAA | POLAR ENERGY |
4ABAE | CONVERTER USB/RS485 |
4A485 | OPTION RS485 |
4AALM | OPTION 2 ALARMS |
4ADIN | OPTION 2 DIGIT |
4AVDC | OPTION 12-24 |
41VDC | OPTION 48-60 VDC |